CGMZB - HALON 1301 AND GLC-13B1

  • MSDS: CGMZB
  • Manufacturer: GREAT LAKES CHEMICAL CORP
  • Product Name: HALON 1301 AND GLC-13B1
  • National Stock Number: 4210-01-359-4769
Product Identification

Product ID:HALON 1301 AND GLC-13B1
MSDS Date:06/01/1993
FSC:4210
NIIN:01-359-4769
MSDS Number: CGMZB

Responsible Party
GREAT LAKES CHEMICAL CORPORATION
HIGHWAY 52 NW
WEST LAFAYETTE, IN 47906
US

Emergency Phone: 501-862-5141 OR 317-463-2511

Info Phone: 317-497-6100

Preparer: RESEARCH SERVICES DEPT.

Cage: 2E394

Contractor
PACIFIC SCIENTIFIC CO HTL/KIN-TECH DIVISION
DUARTE, CA 91010 US

Telephone: 818-359-9317/602-796-1100

Cage: 05167

Ingredients

FREON 1301, TRIFLUOROMONOBROMOMETHANE

CAS: 75-63-8

RTECS: PA5425000

OSHA PEL 6100 MG/CUM

ACGIH TLV: 6090 MG/CUM

Hazards

Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:INHALATION: MAY CAUSE ANESTHETIC &
CARDIAC EFFECTS AT CONCENTRATIONS >10% BY VOLUME. PROLONGED
EXPOSURE TO CONCENTRATIONS >10% (15-20%) MAY LEAD TO POSSIBLE
DEATH.
Explanation of Carcinogenicity:NONE
Effects of Overexposure:INTOXICATION, UNCONSCIOUSNESS
Medical Cond Aggravated by Exposure:CARDIAC CONDITIONS.

First Aid

First Aid:INHALATION: REMOVE TO FRESH AIR. GIVE CPR/ OXYGEN IF
NECESSARY. SKIN: FLUSH W/WATER. EYES: FLUSH W/WATER. OBTAIN MEDICAL
ATTENTION IN ALL CASES. NOTE: EPINEPHRINE IS CONTRAINDICATED IN THE
TREATMENT O F OVER-EXPOSURE TO THIS PRODUCT.

Fire Fighting

Flash Point:NON-FLAMMABLE
Extinguishing Media:WATERSPRAY/MEDIA SUITABLE FOR FLAMMABLE MATERIALS
IN THE AREA.
Fire Fighting Procedures:WEAR SELF CONTAINED BREATHING APPARATUS. USE
WATER SPRAY TO COOL CYLINDERS INVOLVED IN FIRES.
Unusual Fire/Explosion Hazard:>1000F, HALON MAY RELEASE HYDROGEN
FLUORIDE, HYDROGEN BROMIDE, CARBONYL FLUORIDE & CARBONYL BROMIDE.

Accidental Release

Spill Release Procedures:EVACUATE AREA. WEAR SELF CONTAINED BREATHING
APPARATUS. VENTILATE ENCLOSED AREAS IN CASE OF DISCHARGE.

Handling

Handling and Storage Precautions:PROTECT CYLINDERS FROM PHYSICAL
DAMAGE. STORAGE TEMPERATURE SHOULDN'T EXCEED 125F. CYLINDERS SHOULD
BE SECURED STORED W/VALVE PROTECTION CAP IN PLACE.
Other Precautions:DETERMINE THAT PIPING IS EMPTY BEFORE DOING
MAINTENANCE WORK. PERIODICALLY CHECK CYLINDERS TO ENSURE VALVES
AREN'T LEAKING. AVOID PROLONGED EXPOSURE TO EXCESSIVE
CONCENTRATIONS.

Exposure Controls

Respiratory Protection:WEAR NIOSH APPROVED, SELF CONTAINED BREATHING
APPARATUS AT CONCENTRATIONS >10,000 PPM.
Ventilation:LOCAL EXHAUST: FOR MATERIAL TRANSFER & HANDLING. MECHANICAL
(GENERAL): FOR INDOOR AREAS.
Protective Gloves:LINED NEOPRENE/LEATHER
Eye Protection:CHEMICAL SAFETY GOGGLES
Other Protective Equipment:NONE
Work Hygienic Practices:DON'T WEAR CONTACT LENSES.
Supplemental Safety and Health

Chemical Properties

HCC:G3
Boiling Pt:B.P. Text:-72F,-58C
Melt/Freeze Pt:M.P/F.P Text:-270F,-168C
Vapor Pres:62
Vapor Density:5.1
Spec Gravity:1.57
Solubility in Water:0.03%/WT
Appearance and Odor:COLORLESS GAS W/NO ODOR

Stability

Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, FIRES OF METAL HYDRIDES & MATERIAL CONTAINING OWN OXYGEN
Stability Condition to Avoid:FLAMES, HOT SURFACES, SMOKING
Hazardous Decomposition Products:HYDROGEN FLUORIDE, HYDROGEN BROMIDE,
BROMINE, CABONYL FLUORIDE, CARBONYL BROMIDE

Disposal

Waste Disposal Methods:RETURN CYLINDERS TO GREAT LAKES CHEMICAL
CORPORATION, EL DORADO, ARKANSAS. DISPOSE OF IN ACCORDANCE W/LOCAL,
STATE & FEDERAL REGULATIONS. NON-FLAMMABLE GAS UN1956. UN1009.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.